Seismic
Restraint of
Electrical Services
1.
All
electrical conduit 2 1/2"
(64mm) in diameter and larger shall be restrained with specification
type 12
seismic cable restraints or specification type 13 for seismic solid
brace
restraints.
2.
All
electrical bus ducts, cable
trays and ladder trays shall be restrained with specification type 12,
seismic
cable restraints or specification 13 seismic solid brace restraints.
3.
Transverse
restraints shall occur
at 30' (9m) intervals or both ends if the electrical run is less than
the
specified interval. Transverse
restraints shall be installed at each electrical services turn and at
each end
of the electric run.
4.
Longitudinal
restraints shall occur
at 60' (9m) intervals with at least one restraint per electric run. Transverse restraints for one electric
section may also act as a longitudinal restraint for a duct for an
electric
section connected perpendicular to it if the restraints are installed
within 4'
(1.2m) of the intersection of the electric run and if the restraints
are sized
for the larger electric run.
5.
All rigid
floor mounted equipment
must have a resilient media between the equipment mounting hole and the
anchor
bolt. Anchor bolts shall be designed in
accordance with
6.
section
1.06 seismic forces. Neoprene bushings
shall be specification type
4 and anchor bolts shall be specification type 18 or 19.