SEISMIC
PIPING DESIGN GUIDE
Vibration
Isolation of Piping
A.
Horizontal pipe isolation:
The first three pipe hangers in the main lines near the
mechanical
equipment shall be as described in specification
11. Specification
11
hangers must also be used in all transverse braced isolated locations. Brace hanger rods with SRC clamps specification
14. Horizontal
runs in
all other locations
throughout the building shall be isolated by hangers as described in
specification
10. Floor
supported
piping shall rest on
isolators as described in
specification
6. Heat
exchanger's and expansion tanks are considered part of the piping run. The first three isolators from the isolated
equipment will have the same static deflection as specified for the
mountings
under the connected equipment. If piping
is connected to equipment located in basements and hangs from ceilings
under
occupied spaces the first three hangers shall have 0.75" (19mm)
deflection
for pipe sizes up to and including 3" (75mm), 1 1/2" (38mm)
deflection for pipe sizes up to and including 6" (150mm), and 2 1/2"
(64mm) deflection thereafter. Hangers
shall be located as close to the overhead structure as practical. Where piping connects to mechanical equipment
install specification 23
expansion joints or specification
24
stainless hoses if 23 is not suitable for the service.
B. Vertical Pipe Riser isolation: Risers shall be suspended from specification 10 hangers or supported by specification 5 mountings, anchored with specification 25 anchors, and guided with specification 26 sliding guides. Steel springs shall be a minimum of 0.75" (19mm) except in those expansion locations where additional deflection is required to limit load changes to + 25% of the initial load. Submittals must include riser diagrams and calculations showing anticipated expansion and contraction at each support point, initial and final loads on the building structure, spring deflection changes and seismic loads. Submittal data shall include certification that the riser system has been examined for excessive stresses and that none will exist in the proposed design.
Seismic
Restraint of
Piping

1.
Seismically
restrain all piping listed
as a, b or c below. Use specification 12
cables if isolated. Specification 12 or
13 restraints may be used on un-isolated piping.
·
ALL Fuel
oil piping, gas piping,
medical gas piping, and compressed air piping
·
Piping
located in boiler rooms,
mechanical equipment rooms, and refrigeration equipment rooms that is 1
1/4" (32mm) I.D. and larger.
·
All other
piping 2 1/2" (64mm)
diameter and larger.
3.
Longitudinal
restraints shall be at
80' (24m) maximum spacing for all pipe sizes, except where lesser
spacing is
required to limit anchorage loads.
4.
Where
thermal expansion is a
consideration, guides and anchors may be used as transverse and
longitudinal
restraints provided they have a capacity equal to or greater than the
restraint
loads in addition to the loads induced by expansion or contraction.
5.
For fuel
oil and all gas piping
transverse restraints must be at 20' (6m) maximum and longitudinal
restraints
at 40' (12m) maximum spacing.
6.
Transverse
restraint for one pipe
section may also act as a longitudinal restraint for a pipe section of
the same
size connected perpendicular to it if the restraint is installed within
24" (600m) of the elbow or TEE or combined stresses are within
allowable
limits at longer distances.
7.
Hold down
clamps must be used to
attach pipe to all trapeze members before applying restraints in a
manner
similar to clevis supports.
8.
Branch
lines may not be used to
restrain main lines.
9.
Cast iron
pipe of all types, glass
pipe and any other pipes joined with a four band shield and clamp
assembly in
Zones 2B, 3 and 4 shall be braced as in sections C.2 and 3 above.